Draytonville Water Dist (Sc1120003)
PWSID SC1120003 ยท Gaffney, South Carolina ยท serves 5,456 people ยท surface water source
F
Failing
PFAS test results (EPA UCMR 5)
| Contaminant | Result | Federal limit (MCL) | Sampled |
|---|---|---|---|
| PFOS | 19.4 ppt | 4 ppt | 7/12/2023 |
| PFOS | 16.4 ppt | 4 ppt | 7/26/2023 |
| PFOA | 16.2 ppt | 4 ppt | 7/26/2023 |
| PFOA | 15.4 ppt | 4 ppt | 7/12/2023 |
| PFOS | 10.7 ppt | 4 ppt | 1/17/2023 |
| PFOA | 9.2 ppt | 4 ppt | 1/17/2023 |
| PFHxS | 5.5 ppt | 10 ppt | 7/12/2023 |
| PFHxS | 5.2 ppt | 10 ppt | 7/26/2023 |
| PFHpA | 5 ppt | โ | 7/12/2023 |
| PFHpA | 4.7 ppt | โ | 7/26/2023 |
| PFPeA | 4.5 ppt | โ | 7/26/2023 |
| PFHxA | 4.3 ppt | โ | 7/12/2023 |
| PFHxA | 4.3 ppt | โ | 7/26/2023 |
| PFPeA | 4.2 ppt | โ | 7/12/2023 |
| PFHxA | 3.5 ppt | โ | 1/17/2023 |
| PFHxS | 3.5 ppt | 10 ppt | 1/17/2023 |
| PFHpA | 3.5 ppt | โ | 1/17/2023 |
| PFBS | 3.2 ppt | โ | 7/12/2023 |
| PFBS | 3.1 ppt | โ | 7/26/2023 |
ppt = parts per trillion (ng/L). Rows highlighted red meet or exceed the 2024 federal limit.
Violation history
| Date | Violation | Type | Health-based | Status |
|---|---|---|---|---|
| 2022-01-01 | TTHM | MCL | Yes | Resolved |